Note: Truck load can be mixed to make a truck or mixed to make one pallet.
- Application/Description:
-
R-410A has replaced R-22 as the preferred refrigerant for use in residential and light commercial air-conditioning and heat pump systems. It has a higher cooling capacity than R-22 and is significantly higher in pressure. R410A was not designed to retrofit existing R22 systems and should be used only in systems specifically designed for R-410A. It is non toxic and non flammable meeting the highest A1/A1 classification.
-
Chemical Name: R-125(50%), R-32(50%)
Chemical Formula: Blend
Refrigerant Type: HFC
Refrigeration Oils: Polyolester (POE)
Net Weight: 25 lbs. / 100 lbs. / 850 lbs. / 1,450 lbs.
Molecular Weight: 72.6
Boiling Point: (1 atm, °F): -61
Critical Pressure: (psia): 691.8
Critical Temperature: (°F): 158.3
Critical Density: (lb./ft³): 34.5
Liquid Density: (70°F lb/ft³): 67.74
Vapor Density: (bp, lb./ft³): 0.261
Heat of Vaporization: (bp, BTU/lb.): 116.8
Specific Heat Vapor: (1 atm, 70°F, BTU/lb. °F): 0.1953
Specific Heat Liquid: (70°F, BUT/lb. °F): 0.3948
Ozone Depletion Potential: (CFC 11=1.0): 0
Global Warming Potential: (CO2=1.0): 2088
ASHRAE Standard: 34 Safety Rating: A1
Temperature Glide: (°F): 2